PRS-7973 Multifunction Fault Recorder
PRS-7973 fault recording and ranging equipment is used to record the whole process of change of electrical quantities such as current, voltage, frequency, and their derived quantities (active power and reactive power etc.) as well as relevant non-electrical quantities during various faults in the power system, e.g. short circuit, oscillation, frequency collapse, and voltage collapse etc.
https://global.sznari.com/upload/images/product/20230829/16932779579279048.png
Scope of Application

PRS-7973 fault recording and ranging equipment adopts centralized design concept and allows flexible configuration according to engineering demands. It can serve both as fault recording and ranging equipment for power systems of various voltage levels and as unit fault recording and analysis equipment for power generation units of various capacities.

Advantages
01
The device is based on Linux system programming, multi-process, multi-thread, reasonable use of system resources and scheduling mode, to ensure the reliability, real-time performance and safety of the monitoring system.
02
The device adopts an industrial-grade database management system (DBMS) to ensure efficient and safe data storage and retrieval of data in a distributed network.
03
The device adopts the platform design concept, the platform and application uses complete decoupling design, the data is managed in a unified manner, the protocol is modularized and service-oriented, and friendly configuration is realized.
04
The device fault recording module has powerful functions. Based on the ComTrade file format, graphs can be scaled arbitrarily, and can perform vector diagram analysis, harmonic analysis, and curve operation (curves include positive sequence components, negative sequence components, zero sequence components, differential currents, braking currents, sudden changes, etc.) and impedance analysis.
05
Provides capture and analysis functions of SV, GOOSE, MMS, CMS and other network messages, monitors and analyzes the message situation at any time.
06
The system focuses on the visual monitoring of virtual terminals between protections, visually displays and monitors the interaction details between protections.
07
Provides a professional SCD model file management and control module, and provides professional intelligent diagnosis analysis and suggestion functions.
08
Focuses on the network communication monitoring of protection equipment and switches, and can accurately locate faults.
09
Intelligently analyzes defects such as secondary equipment body abnormalities, process layer circuit abnormalities, and tripping and closing circuit abnormalities, and gives the cause of the problem and suggestions for handling, reducing the difficulty of problem handling and improving handling efficiency.
010
Conducts real-time analysis of online monitoring data such as the working voltage, temperature, and optical power of the secondary equipment, discovering hidden faults of the secondary equipment, and sending early warning.
Technical Features
Control unit
Acquisition unit parameters

CPU

Single CPU: ≥4 core, dominant frequency≥3.0GH

or multiple CPUs: ≥4 core, dominant frequency≥2.2GHz  

Memory


Hard drive capacity

≥ 2 hard drives, each 1TB

Ethernet port

≥ 6 / host

System mean time between failures (MTBF)

≥ 30000h

Annual availability of system

≥ 99%

Screen response time when calling real-time data

≤ 2 s

Query response time

≤ 30 s

Incident report transmission time

≤ 5 s

Wave recording file transmission time

≤ 30 s

General remote metering transmission time

≤ 20 s

Network communication state change time at station level  

≤ 1min

Fault briefing time

≤ 10 s

System alarm accuracy

100%

Onsite equipment control accuracy

100%

Continuous message record

≥3 days (average flow≤200Mbps, non-SV ratio ≤10%)

≥7 days (average flow≤200Mbps, non-SV ratio≤10%)

Steady-state wave recording record

≥7 days (sampling frequency: 2000Hz or 1000Hz)

Transient-state wave recording record

3000 times (sampling frequency: 10000Hz or 4000Hz)

Abnormal message event record

≥10000

Abnormal message record

≥5000

Message record capturing rate

100%

Message record data integrity rate

100%