(1) The integrated anti-maloperation(i.e.,the SCADA is both monitor andanti-maloperation machine),when the SCADA runand receive signal normally.
The troubleshooting method is:
a.Check whether the communication between the anti-maloperation host and key base key base is normal.
b. If the SCADA is redundant mode onsite,check whether the anti-maloperation key base is connected to the host.
(2)Independent anti-maloperation(i.e.usingthe anti-maloperation system made by external manufacturer,such as UNITECH or CYG).
The troubleshooting method is:
a.Check whether the anti-maloperation system point table in thedatabase configuration tool is consistent with the anti-maloperation manufacturer.and pay attention to their respective starting points
b. Check whether their communication protocols are consistent.