The alarm indicator of main transformer backup protection is on during operation.

Themain transformerbackupprotection reports long-time action and alarm action ofcompound voltage blocking during operation.

The troubleshooting method is:

In general, operation is carried out onsite, direct shutdown of busbar on the medium voltageside ofmain transformer leads to adjacent multi-voltage locking contact of backup protection on medium voltage side, the backup protection on highvoltage side is blocked, and this is a normal situation.

Polarity problem of busbar protection

Whether the polarity ofbusbar protection needs to be fixed? If it needs to be fixed, how to fix it?

The troubleshooting method is:

Thepolar ends ofCT in various branches must be consistent; in the device, theCT polarity ofbus couplershould be the same as that of branch on busbar II by default, and theCT polarity of section 1 and section 2 should be the same as theCT polarity of various branches. The bay ofbus coupler 1 should be fixed asL1, the bay of section 1 should be fixed asL23, and the bay of section 2 should be fixed asL24.

Whether the new main transformer has fixed branch in busbar differential protection?

In busbar protection onsite, the branches of main transformers have fixed bays.

The troubleshooting method is:

The bays of main transformer branches are fixed as L2, L3, L14 and L15, corresponding to main transformers 1~4, respectively.

The total fault signal of protection device is not maintained

After the protection device has sent thetotal fault signal, the signal is reset automatically.

The troubleshooting method is:

According to the new regulations ofSouth Grid, the protection device needs toautomatically reset the signal after sending thetotal fault signal.

How to choose the synchronization method of measuring and control device?

Selection ofsynchronization method

The troubleshooting method is:

Themeasuring and control device is equipped with different programs for different regions. In theSouth Grid, thesynchronization method ofmeasuring and control device is determined according to the setting values; in the State Grid, thesynchronization method ofmeasuring and control device is selected according to the remote control channel selected by background.