The BP-2C is a numerical busbar
differential protection intended for protecting and monitoring various
busbars of various voltage level, ranging from 1000kV to 35kV. BP-2C can
detect and clear all types of internal falults.BP-2C provides fast and
selective protection, monitoring and control for single busbar, single
busbar with single bus coupler, double busbar, double busbar with up to 4
bus couplers, 3/2 breaker busbar, etc. The relay can operate correctly
over a wide frequency range in order to accommodate power system
frequency variations during disturbances.This relay can sample the
analog values from the traditional instrument transformers, or receive
the sampled values from the electronic current and voltage transformers
(via a merging unit). The binary inputs and outputs of this relay can be
configured according to the demands of a practical engineering through
the PRS IED Studio configuration tool auxiliary software, which can meet
some special requirements of protection and control functions.This
relay can fully support the IEC61850 communication protocol and GOOSE
function, and can completely meet the demands of a modern digitalized
substation.
01
This device can sample the analog values from the traditional instrument transformers, or receive the sampled values from the electronic transformers. It can support the protocol IEC60044-8, IEC61850-9-2 and GOOSE.
02
This device can communicate with a SAS or RTU via different communication intermediates: thernet network, RS-485 serial ports. The communication protocol of this device is optional: IEC61850, IEC60870-5-103, DNP3.0 or ModBus.
03
This device can detect the tripping circuit of the circuit breaker and monitor the operation (close or trip) time of a circuit breaker by checking the auxiliary contacts of the circuit breaker.
04
Complete event recording function is provided: 512 latest protection operation reports, 512 latest supervision records, 128 latest control operation records, 128 latest user operation records and 2000latest records of time tagged sequence of event (SOE) can be recorded.
05
Powerful fault and disturbance recording function is supported: 64 latest fault or disturbance waves, the duration of a wave recording is configurable.
06
This device is based on a 32-bit high performance dual-core processor, internal high speed bus and intelligent I/O ports, and the hardware is in modularized design and can be configured flexibly, featuring interchangeability and easy extension and maintenance.
07
Modularized hardware design makes this relay be easily upgraded or repaired by a qualified service person. Various function optional modules can satisfy various situations according to the different requirements of the users..
08
The adoption of 16-bit A/D converter and the dual-channel sampling technology can ensure the accuracy and reliability of protection sampling and the correctness of protection operation. It also provides dedicated current transformers for metering, and ensures the high accuracy of telemetering with 48-point high speed sampling rate per cycle.
09
Various algorithms for protection and measurement have been completed in this device for the feature of electronic transformer sampling, such as the error prevention method of multi-algorithms data anomaly for the digital channels, to realize high accuracy and reliability under various conditions of network faults or communication interruption.
010
This device has powerful GOOSE functions, and the connection and cooperation between some devices can be realized without using electrical cables, to facilitate the realization of such functions as simple bus differential protection, overload interlock shedding function and backup automatic transfer function etc.
011
This device has fully realized the technology to integrate six functions into one device: protection, measurement, control, remote signaling, merging unit function and remote module functions, to improve the reliability.
012
Various methods of GPS time synchronization are supported in this relay, including SNTP, pulse per second (PPS) and IRIG-B synchronization.
013
The protection modules are completely separated from other modules, and are independent in both hardware and software. The protection functions do not depend on the communication network, so the failure of communication network will not affect the normal operation of the protection functions.
014
Mature protection configuration, fast speed and high security performance can meet the practical requirements. Each protective element is independent, so it is very convenient for whether adopting the selected protective element.
015
This device constantly measures and calculates a large amount of analog quantities, such as phase voltage, phase-to-phase voltage, neutral voltage, phase current, neutral current, active power, reactive power, power factor and frequency etc.
016
The human machine interface (HMI) with a small control module (a 240×128-dot LCD, a 9-key keypad and 19 LED indicators) on the front panel is very friendly and convenient to the user.