PRS-7367 Protection and Control Unit

The PRS-7367 is a numerical distributed protection intended for protecting and monitoring various primary apparatus including overhead line, underground cable, transformer, capacitor, etc. PRS-7367 can be used in various voltage level, generally ranging from 10kV to 35kV. PRS-7367 can detect and clear all types of internal phase-to-phase.


PRS-7367 provides fast and selective protection, monitoring and control for feeders and capacitors. The relay can operate correctly over a wide frequency range in order to accommodate power system frequency variations during disturbances.


This relay can sample the analog values from the traditional instrument transformers, or receive the sampled values from the electronic current and voltage transformers (via a merging unit). The binary inputs and outputs of this relay can be configured according to the demands of a practical engineering through the PRS IED Studio configuration tool auxiliary software, which can meet some special requirements of protection and control functions.


This relay can fully support the IEC61850 communication protocol and GOOSE function, and can completely meet the demands of a modern digitalized substation.

https://global.sznari.com/upload/images/product/20230904/16937971927303532.png
Scope of Application
The PRS-7367 is a numerical distributed protection intended for protecting and monitoring various primary apparatus including overhead line, underground cable, transformer, capacitor, etc.
Advantages
01
l This device is based on a 32-bit high performance dual-core processor, internal high speed bus and intelligent I/O ports, and the hardware is in modularized design and can be configured flexibly, featuring interchangeability and easy extension and maintenance.
02
l Modularized hardware design makes this relay be easily upgraded or repaired by a qualified service person. Various function optional modules can satisfy various situations according to the different requirements of the users..
03
l The adoption of 16-bit A/D converter and the dual-channel sampling technology can ensure the accuracy and reliability of protection sampling and the correctness of protection operation. It also provides dedicated current transformers for metering, and ensures the high accuracy of telemetering with 48-point high speed sampling rate per cycle.
04
l This device can sample the analog values from the traditional instrument transformers, or receive the sampled values from the electronic transformers. It can support the protocol IEC60044-8, IEC61850-9-2 and GOOSE.
05
l Various algorithms for protection and measurement have been completed in this device for the feature of electronic transformer sampling, such as the error prevention method of multi-algorithms data anomaly for the digital channels, to realize high accuracy and reliability under various conditions of network faults or communication interruption.
06
l This device has powerful GOOSE functions, and the connection and cooperation between some devices can be realized without using electrical cables, to facilitate the realization of such functions as simple bus differential protection, overload interlock shedding function and backup automatic transfer function etc.
07
l This device has fully realized the technology to integrate six functions into one device: protection, measurement, control, remote signaling, merging unit function and remote module functions, to improve the reliability.
08
l Various methods of GPS time synchronization are supported in this relay, including SNTP, pulse per second (PPS) and IRIG-B synchronization.
09
l The protection modules are completely separated from other modules, and are independent in both hardware and software. The protection functions do not depend on the communication network, so the failure of communication network will not affect the normal operation of the protection functions.
010
l Mature protection configuration, fast speed and high security performance can meet the practical requirements. Each protective element is independent, so it is very convenient for whether adopting the selected protective element.
011
l Mature protection configuration, fast speed and high security performance can meet the practical requirements. Each protective element is independent, so it is very convenient for whether adopting the selected protective element.
012
l This device constantly measures and calculates a large amount of analog quantities, such as phase voltage, phase-to-phase voltage, neutral voltage, phase current, neutral current, active power, reactive power, power factor and frequency etc.
013
l The human machine interface (HMI) with a small control module (a 240×128-dot LCD, a 9-key keypad and 21 LED indicators) on the front panel is very friendly and convenient to the user.
014
l This device can communicate with a SAS or RTU via different communication intermediates: thernet network, RS-485 serial ports. The communication protocol of this device is optional: IEC61850, IEC60870-5-103, DNP3.0 or ModBus.
015
l This device can detect the tripping circuit of the circuit breaker and monitor the operation (close or trip) time of a circuit breaker by checking the auxiliary contacts of the circuit breaker.
016
l Complete event recording function is provided: 512 latest protection operation reports, 512 latest supervision records, 128 latest control operation records, 128 latest user operation records and 2000latest records of time tagged sequence of event (SOE) can be recorded.
017
l Powerful fault and disturbance recording function is supported: 64 latest fault or disturbance waves, the duration of a wave recording is configurable.
Technical Features
IEC 60617
ANSI
CYG Code

Description

IEC 60617

Non-directional overcurrent protection

3I>

Directional overcurrent protection

3I> ->

Non-directional earth-fault protection

Io>

Directional earth-fault protection

Io>->

Switch onto fault

SOTF

Circuit breaker failure protection

3I>/I0>BF

Three-phase thermal overload protection

3lth>

Phase discontinuity protection

I2/I1>

Negative sequence current protection

I2>

Three-phase overvoltage protection

3U>

Positive sequence overvoltage protection

U1>

Residual overvoltage protection

Uo>

Negative sequence overvoltage protection

U2>

Three phase under voltage protection

3U<

Positive sequence undervoltage protection

U1<

Overfrequency protection

f>

Underfrequency protection

f<

Underfrequency restore protection

-

Frequency gradient protection

Df/dt<>

Auto-recloser

O ->I

Synchrocheck

SYNC

Current circuit supervision

MCS 3I

Fuse failure supervision

FUSEF

Trip circuit supervision

TCS

Current unbalance protection

dI>C

Three phase current unbalance protection

3dI>C

Voltage unbalance protection

PQUUB

Three phase voltage unbalance protection

PQUUB

Fault locator

FLOC

Three phase under voltage protection of capacitor

3U<

Reverse power protection

P>

Voltage Selection

/

Mechanical Protection


Trip Logic

/

Close Logic

/

Backup power automatic switch

/

Wattmetric sensitive earth fault

/

Description

ANSI

Non-directional overcurrent protection

50/51P

Directional overcurrent protection

67P

Non-directional earth-fault protection

50/51N

Directional earth-fault protection

67N

Switch onto fault

SOTF

Circuit breaker failure protection

50BF

Three-phase thermal overload protection

49

Phase discontinuity protection

46PD

Negative sequence current protection

46N

Three-phase overvoltage protection

59

Positive sequence overvoltage protection

47

Residual overvoltage protection

59G

Negative sequence overvoltage protection

47

Three phase under voltage protection

27

Positive sequence undervoltage protection

47

Overfrequency protection

81

Underfrequency protection

81

Underfrequency restore protection

-

Frequency gradient protection

81

Auto-recloser

79

Synchrocheck

25

Current circuit supervision

MCS 3I

Fuse failure supervision

60

Trip circuit supervision

TCM

Current unbalance protection

51NC-1

Three phase current unbalance protection

51NC-2

Voltage unbalance protection

PQUUB

Three phase voltage unbalance protection

PQUUB

Fault locator

21FL

Three phase under voltage protection of capacitor

27

Reverse power protection

32R/32O

Voltage Selection

/

Mechanical Protection


Trip Logic

94

Close Logic

/

Backup power automatic switch

/

Wattmetric sensitive earth fault

/

Description

CYG Code

Non-directional overcurrent protection

50/51P/51PVT

Directional overcurrent protection

67P

Non-directional earth-fault protection

50/51G/51GVT

Directional earth-fault protection

67G

Switch onto fault

SOTF

Circuit breaker failure protection

50BF

Three-phase thermal overload protection

49F

Phase discontinuity protection

46D

Negative sequence current protection

46N

Three-phase overvoltage protection

59

Positive sequence overvoltage protection

59P

Residual overvoltage protection

59G

Negative sequence overvoltage protection

59N

Three phase under voltage protection

27

Positive sequence undervoltage protection

27P

Overfrequency protection

81O

Underfrequency protection

81URS

Underfrequency restore protection

81URE

Frequency gradient protection

81R

Auto-recloser

79

Synchrocheck

25SYN

Current circuit supervision

CTS

Fuse failure supervision

PTS

Trip circuit supervision

TCS

Current unbalance protection

51NA

Three phase current unbalance protection

51NT

Voltage unbalance protection

59NA

Three phase voltage unbalance protection

59NT

Fault locator

21FL

Three phase under voltage protection of capacitor

CUB_27

Reverse power protection

32R

Voltage Selection

/

Mechanical Protection

MP

Trip Logic

94T

Close Logic

Close Logic

Backup power automatic switch

BPAS

Wattmetric sensitive earth fault

SEF

Related solutions
https://global.sznari.com/upload/images/article/20230904/16938141477206261.jpg
Power Plant (Thermal Power/Hydro Power) Substation NCS System Solution
The PRS-7000 power plant power network control system (NCS) integrates various functions, such as anti-maloperation locking, intelligent equipment information integration,remote control communication, protection information management and local monitoring. This system can be seamlessly connected to the protection, measurement and control device and intelligent equipment from different manufacturers, so as to complete information processing, display and monitoring of step-up substation of power plant, facilitate monitoring and control of equipment, and provide reliable assurance for the safe and economical operation of the step-up substation.
https://global.sznari.com/upload/images/article/20230911/16944065402099444.jpg
Centralized PV Power Station Solution
CYG SUNRI provides centralized PV power plant solution, including remote central control,integrated substation automation system, power forecasting, power control,CCTV and micro-computer inter-locking systemin case of mal-operation. The provided system equipment complies with thepowergrid connection specificationfor PV power stations. Moreover, advanced technical measures are provided to ensure the safe and stable operation of PV powerstation and carry out organization, coordination and operation management activities in a scientific and efficient way, whichcan help improve the work efficiency of operators, ensure the reliable operation of PV power station, and improve the safety management and economic benefits of PV power station.
https://global.sznari.com/upload/images/article/20230904/16938294797102702.jpg
Distributed PV Power Generation Solution
CYG SUNRI provides primary and secondary integrated solutions of distributed PV power generation, which can meet the requirements of deployment and application in various scenarios. By following the principles of adaption to local conditions, cleanness and efficiency, dispersed layout, and nearby utilization, the local solar energy resources are fully utilized. It is convenient to start and stop power, and the investment is small with quick returns. Related solutions comply with relevant standards and specifications, and combined with specialized and efficient secondary equipment and operation & maintenance systems, this solution can enable smooth connection to grid by users.
https://global.sznari.com/upload/images/article/20230904/16938295688440856.jpg
Overall Solution Of Wind Power Plant
According to the requirements forwind power generation,CYG SUNRI provides solutions such as remote centralized control, integrated automation of substation, power forecasting, power control, video monitoring, and microcomputer inter-locking systemin case of mal-operation,to ensure smooth grid connection of windpower plant,improve safety management and economic benefits of windpower plant, and reduce the construction and investment risks. (1) Land centralized wind power generation solution: It can meet the comprehensive monitoring, grid connection and dispatching requirements of windpower plants, and provide comprehensive real-time monitoring of wind turbines, anemometer tower, box transformer,step-up substation, and environmental monitoring system. (2) Land distributed wind power generation solution: It has achieved the core objective of "unattended, attended with fewer persons and regional maintenance" of substations and plants, a visual monitoring platform withdual structure of C/S and B/S is provided, and centralized monitoring and management of multiple unattended stations is implemented. (3) Offshore wind power generation solution:The system can provide remote monitoring and control of the equipment in the land metering station and the offshore step-up substation, and achieve various closed-loop control functions according to the requirements of the power grid operation mode.